… & How to Avoid Them
This article identifies common errors that structural engineers make
when performing seismic design and calculations. The intent is to help
engineers avoid those errors and misapplications. This article is
written in checklist format such that an engineer can verify adequate
self-knowledge, as well as review the work of others on a project.
It is based upon the 2012
International Building Code
(IBC), the American Society of Civil Engineers’ ASCE/SEI 7-10, the
American Concrete Institute’s ACI 318-11, the American Institute of
Steel Construction’s AISC 360-10, AISC 341-10, and other current
standards. For ease of identification, referenced sections are noted in
brackets and refer to ASCE/SEI 7-10 section numbers, unless otherwise
noted.
1) Seismic Design Category A
When in seismic design category (SDC) A, it is not necessary to use
any of the provisions of Chapter 12. Instead, the general structural
integrity provisions of Section 1.4 apply. Note that these provisions
include some loads that may often be erroneously neglected. The required
lateral forces include 1% of dead load, 5% of dead plus live load for
beam (axial load) connections, and 20% of wall weight for wall
connections. Non-structural components in SDC A are exempt from seismic
design requirements.
See [1.4], [11.4.1], and [11.7].
2) Importance Factor
The importance factor is based upon the risk category and the
associated life safety, hazard or essential nature of the structure.
Both [
Table 1.5-1] and [
IBC Table 1604.5] should be reviewed. A typical building can sometimes evolve into an I
e
equal to 1.25 or 1.5 when occupancy or use expands. Examples include
relatively small churches (expanding to an occupancy greater than 300)
or a building where hazardous materials are stored. It should be noted
that for building design, I
e = 1.0, 1.25, or 1.5; but for non-structural components, I
p = 1.0 or 1.5 only [
13.1.3], such that I
p may not equal I
e, and in some instances I
p may be less than I
e. See [
11.5.1] and [
Table 1.5-2].
3) Continuous Load Path
ASCE/SEI 7-10 has very specific provisions for many elements such as
collectors, connections, diaphragms, walls, etc. However, in addition to
those specifics, the engineer is required to provide a continuous load
path for all inertial forces from their origin to the foundation. Such
load paths must conform to the relative stiffness and strength of the
elements that exist in the structure. See [
12.1.3].
4) R Factor
The response modification coefficient, R, is part of a concept where
an elastic design may be performed, but with due consideration of the
overstrength and ductility inherent in the lateral force resisting
system. In order to ensure reliability, many requirements are triggered
with each R factor. The “R” Tables, [
Table 12.2-1] and [
Table 15.4-1, 2],
list the corresponding detailing requirements. The “strings attached”
can be extremely significant, especially for concrete structures that
fall under ACI 318-11 Chapter 21 and steel structures with R greater
than 3 (AISC 341
Seismic).
5) Irregularity Triggers
[
Table 12.3-1] and [
Table 12.3-2] describe various
horizontal and vertical irregularities, respectively, which trigger
specific provisions. Each referenced section must be reviewed. Triggered
provisions include modal analysis, three-dimensional analysis,
redundancy factor, force amplification, torsion amplification, and
collector force increases.
See [12.3.2.1] and [12.3.2.2].
6) Overstrength – Ωo
The variable Ω
o is an amplification factor applied to the
forces in certain elements in the seismic load path. It is required so
as to prevent a weak link from occurring prior to the full energy
dissipation and ductility potential of the primary
lateral-force-resisting system. For example, in a steel braced frame, in
order for the diagonal brace to yield and dissipate energy in a
controlled and reliable manner, all other portions of the load path
(e.g., connections, bolts, welds, gusset plates, anchor bolts, columns
and collectors) need to be stronger than the maximum anticipated
strength or force in the brace. Therefore, Ω
o amplification
and load combinations are specifically triggered for those elements, in
the sections mentioned below and in Material Standards such as AISC
341-10 and ACI 318-11. For example, AISC 341-10 states that anchor bolt
forces must be amplified by Ω
o, which is typically 2.0 or
greater. This applies to all steel buildings where R is greater than 3,
unless you can prove otherwise via an advanced and rigorous analysis.
See [12.4], [12.2.5.2], [12.10.2.1], [12.3.3.3], [12.13.6.5], and [AISC 341 when R>3, ACI Chapter 21, Appendix D, etc.].
7) Redundancy – Rho
Rho is a factor that penalizes structures that do not have
redundancy. Rho is equal to either 1.0 or 1.3. Rho is equal to 1.0 for
SDC B and C, for drift calculations, non-structural component forces,
collectors, Ω
o load combinations, and diaphragms.
See [12.3.4].
8) Vertical Seismic Load Effect – Ev
[
12.4.2.2] requires that a vertical load effect equal to 0.2 S
Ds
be applied to dead load. It is applied as a dead load factor adjustment
and may act downward or upward. It is at the strength design level, so
it may be multiplied by 0.7 for allowable stress design (ASD). The
values of I
e, I
p, Rho and R are not applied to E
v.
9) Load Combinations and Allowable Stress Design – 0.7 E
For ASD load combinations [
12.4.2.3], [
12.4.2] shall be used in lieu of [
2.3.2] and [
2.4.1].
Earthquake forces are at strength level, so for the ASD combinations,
use 0.7 E. The 0.7 E applies to non-structural component forces (F
p).
See [13.3.1].
10) Orthogonal Effects
Earthquake forces must be calculated for each of the two primary
orthogonal directions. In order to consider the effects of earthquake
forces at some angle other than those two directions, “orthogonal
effects” must be considered. [
12.5] requires that irregular
buildings in SDC C and corner columns in SDC D, E, and F be considered
with 100% of forces in one direction plus 30% in the other. It should be
noted that IEEE 693 (Electrical Equipment) applies orthogonal effects
to all elements, including corner anchor bolts.
11) Effective Seismic Weight
[
12.7.2] defines the effective seismic weight, W. Except for
as mentioned below, live load is not included in the inertial force;
however, the seismic force is later combined with dead and live loads in
the load combinations. [
12.7.2] stipulates that W must include the following masses: 25% of storage live load, partition load of 10 psf [
4.3.2], industrial operating weight and unbalanced conditions, 20% of snow if greater than 30 psf, and weight of roof gardens.
12) Distribute Base Shear over Height
Once the base shear, V, is calculated, it must be distributed over
the height of the structure. For a one-story building, all of the base
shear would be applied at the roof. For multi-story structures, the base
shear must be distributed to each floor, not only in proportion to each
floor’s mass, but also in proportion to the distance of the floor from
the base. A triangular distribution of force results for regular
multi-story buildings. For distributed-mass structures like stacks and
masonry fences, the centroid of the load should result at 2/3 of the
height above the base, not at ½ the height or at the center of gravity.
See [12.8.3].
13) Modal Response Spectrum Analysis
When a structure has significant vertical or horizontal irregularities, the equation [
12.8-12] (triangular force distribution) becomes inaccurate, and therefore a modal response spectrum analysis is required.
See [12.6], [Table 12.6-1] and [12.9]. The purpose is not to refine the magnitude of the base shear, but to perform the following more accurately:
1) Distribute base shear over height.
2) Quantify horizontal torsional effects.
3) Account for higher mode effects.
Note that the “NP” entry in [
Table 12.6-1] includes many
common irregularities, including horizontal type 1a, 1b and vertical
type 1a, 1b, 2 and 3, and thus a modal analysis is triggered for those
structures.
14) Accidental Torsion
In addition to inherent torsion, accidental torsion must be applied.
This is to prevent weak torsional resisting arrangements, as well as
account for unexpected distribution of live load and unexpected
stiffness of structural and non-structural elements. This provision
applies to non-building structures, as well as buildings. For
torsionally irregular buildings, amplification of the accidental torsion
may be required as per [
12.8.4.3].
See [12.8.4.2].
15) Drift Check
Results from the elastic analysis must be amplified by C
d to render expected deflections. Note that C
d is a very large value, typically a factor of about 4 or 5. The drift is then divided by I
e,
because the allowable drifts are organized into a table that considers
risk category. One should be careful when using ASD load combinations
not to apply the 0.7E to drift calculations.
See [12.8.6], [12.12], and [Table 12.12-1].
16) Diaphragm Forces
Forces at lower floor diaphragms may be higher than those used for the lateral force resisting system [
Equation 12.8-12].
This is due to higher mode effects (i.e., modes higher than the first
mode) where the lower floors may be accelerating higher than calculated.
Note that Fpx minimums of [
Equation 12.10-2] often govern for the lower floors.
See [12.10.1.1].
17) Non-structural Components
Non-structural components may also experience higher local
accelerations due to higher mode effects, as well as amplification of
the force within the non-structural element itself.
See [Equation 13.3.1].
Industrial structures often feature very large forces. It is unlikely
that the forces on two different floors would occur at the same point in
time. Therefore, one method of accounting for the forces in a computer
model is to evaluate two conditions.
1) Run a load case with the weight of the equipment included in the
seismic weight of the floor and the base shear, V, distributed over the
height as per [
Equation 12.8-12].
2) Run a load case with only the non-structural component force for
one piece of equipment, so as to verify an adequate load path to the
vertical system and/or foundation.
Note that it is necessary to apply E
v to load combinations with non-structural component forces. The factor Ω
o
does not apply to such load combinations, except in some ACI 318-11
Appendix D calculations. Note also that when non-structural components
get very large – i.e., 25% or more of total structure mass – then [
15.3]
provisions apply. For these heavy components, the stiffness and design
coefficients of both the component and the primary structure must be
considered together in a computer model.
18) Wall Design
Connections to wall panels made of concrete and concrete masonry
units (CMU) have performed poorly in past earthquakes. The equations of [
12.11.1] and [
12.11.2.1] should be implemented, as well as ACI 318-11 Appendix D for anchorage.
19) Foundation Ties
Foundation ties are required as per [
12.13.6.2] in order to
ensure that the foundation system acts as an integral unit, not
permitting one column or wall to move appreciably relative to another.
This applies to pile caps in SDC C, D,E and F, and spread footings for
SDC E and F.
20) Reduction of Foundation Overturning
[
12.13.4] allows for a reduction of the bearing pressures at
the soil-foundation interface. Forces may be reduced by 25% in
recognition that the first mode triangular force distribution will
likely not occur without higher mode effects occurring and negating the
direction of the first mode, resulting in reduced maximum overturning
moments.
21) Errata
The ASCE/SEI 7-10 and IBC 2012 websites have the latest errata for
those documents. Significant entries due to typographical mistakes or
unintended consequences of revisions are corrected in the errata.
22) IBC Overrides
IBC 2012 contains amendments to ASCE/SEI 7-10.
See [IBC 1613], [IBC 1613.5], and [IBC Chapters 18 through 23].
ASCE/SEI 7 is on a six-year update cycle, and IBC is on a three-year
cycle. Technical changes to IBC often have to be approved well before
the issue date. Inevitably, coordination between ASCE 7, IBC and
referenced material standards (e.g. ACI, AISC, etc.) often occur through
errata, supplements or IBC-published amendments. It is essential to
check for these changes periodically. Individual state and local
governments may also adopt amendments that affect projects located
within their jurisdiction.
23) ASCE/SEI 7-10 Third Printing
It is recommended that the user make use of the ASCE/SEI 7-10
Expanded Seismic Commentary,
which provides 135 pages of valuable background information. It is
incorporated in the third printing of ASCE/SEI 7-10 only. For those who
own a first or second printing, you may download a PDF file of the
commentary for free from the ASCE website. This Commentary was developed
by the National Earthquake Hazard Reduction Program/Building Seismic
Safety Council/Provisions Update Committee (NEHRP/BSSC/PUC) and
describes the reasons for the individual provisions of ASCE/SEI 7-10.
Conclusion
A concerted effort to avoid errors is essential. Errors can be
minimized by applying knowledge and experience. This article is intended
to assist in that effort. The above listing of common errors was
developed by the author during frequent reviews of other engineers’
work. It is based upon the author’s experience and should not be
construed as a consensus document prepared or endorsed by the ASCE/SEI
7-10 or NCSEA Seismic Committees.▪